Tuesday, December 4, 2012
Thursday, September 20, 2012
What’s new in Power Quality? Not the Goal! PQM-109
The goal of quality power for your facility or application is
probably still the same:
·
Supply equipment with power that does not cause
malfunction or damage
·
Eliminate penalties from provider or save energy
costs
·
Comply with industry standards
Peace of Mind
What is new in power quality is the ability to model the
solution before it is installed to prove the effectiveness of the solution
giving you peace of mind. This can be
done at the power electronic level which is the most precise.
Achieving the goal is sometimes difficult. You may be faced with a decision between
multiple solutions offered by well meaning manufacturers. Which solution will truly solve your problem
or meet your needs?
Now, your system can be modeled at the actual power
electronic level to predict the performance of your myriad of possible
solutions. Using circuit simulation with a comprehensive
power quality analysis can save you from making an expensive mistake by evaluating
various alternative solutions before you buy them. Like a test drive before you buy it… this can
give you peace of mind.
Thursday, August 16, 2012
What is the function of a line reactor – for thyristor bridge PQM-108
Line reactors are commonly used in adjustable speed drive
applications to improve power quality.
They are connected in series with the input terminals of the drive to
serve multiple functions.
1) Suppress voltage transients, protect
thyristors,
2) Increase effective input impedance resulting
in lower drive input harmonic current distortion and system voltage distortion,
reduce true rms current, improve total (true) power factor.
5% effective impedance (at full
load) yields about 35% THD-I, 3% impedance at full load results in about 45%
THD-i. Note: a drive system with a 5% impedance line reactor, operating at 60%
of reactor current rating will look like a 3% impedance reactor.
3) Reduce
voltage notching upstream of the line reactor. Reactor serves (along with
upstream impedance, ie: transformer) as part of a voltage divider network where
the notch voltage is distributed proportionately across the two impedances. To
solve voltage notching, the line reactor must be connected at the input
terminals of the SCR converter (ie: DC drive) that is producing the voltage
notches.
Thursday, August 2, 2012
What is the function of a line reactor – for diode bridge PQM-107
Line reactors are commonly used in adjustable speed drive
applications to improve power quality. They are connected in series with the input
terminals of the drive to serve multiple functions.
1) suppress
voltage transients enabling drives with a dc bus capacitor to ride thru some
system voltage disturbances, minimize O/V nuisance tripping, protect diodes
from transients, protect dc bus capacitor,
2) Increase
effective input impedance resulting in lower drive input harmonic current
distortion and system voltage distortion, reduce true rms current, improve
total (true) power factor.
5% effective impedance (at full
load) yields about 35% THD-I, 3% impedance at full load results in about 45%
THD-i. Note: a drive system with a 5% impedance line reactor, operating at 60%
of reactor current rating will look like a 3% impedance reactor.
Wednesday, July 25, 2012
What is the best way to mitigate harmonics? PQM-106
There are number of types of equipment that will reduce
harmonic distortion (tuned harmonic filters, line reactors, active harmonic
filters, multi-pulse rectifiers, 5% THD harmonic filters, phase shifting
transformers, etc). Each has its merits
in the proper circumstances. Each has its advantages as well as
disadvantages. Each has a typical
performance and cost. There is no single
method that is best for all cases.
This
best solution will depend on the unique aspects of the power system, facility
operations, type of loads and the target distortion levels. In a facility with many loads, often the best
technical and economical solution involves a combination of methods. An
examination of the single line diagram supplemented by simulation of the power
electronic loads can result in a determination of the best economical and
technical solution to a harmonics concern.
Monday, July 23, 2012
Thursday, July 19, 2012
What harmonic current distortion should I expect from a VFD? PQM-105
An 18-pulse drive to typically will achieve about 4% to 6%
THD-i when operating at full load (assumes balanced and non distorted voltage
source). Distortion will increase as load is reduced and when voltages are not
balanced.
A 12-pulse drive typically achieves 12 – 15% THD-i when
operating at full load, (assuming balanced and non distorted voltage source).
Distortion will increase as load is reduced and when voltages are not balanced.
Filters are available for 12-pulse drives that will reduce current distortion
to 5% or less.
A 6-pulse drive without a DC or AC inductor may be as high
as 60-100% THD-i. However a 6-pulse
drive with 5% line reactor (or equivalent DC choke) achieves about 35% THD-i.
at full load (45% at 60% load) and with 3% line reactor (or equivalent dc
choke) achieves about 45% THD-i at full load (about 60% THDi at 60% load). Filters are available for 6-pulse drives that
will reduce current distortion to 5%, 8%, 10%, 12%.
Thursday, July 12, 2012
What is a Detuned Power Factor (PF) Capacitor? PQM-104
Since power factor capacitors have capacitance reactance
(ohms) that decrease as frequency increases, they will naturally offer a low
impedance path to harmonics. If the power system voltage is distorted, then
current will be driven into the capacitor, at each of the frequencies that are
present in the harmonic voltage spectrum. Additionally, the capacitance
(Farads) will combine with upstream circuit inductance (Henries) to form a
parallel tuned circuit and a series tuned circuit, each with their respective
natural resonant frequency. If harmonic voltage is present at one of these
frequencies, then harmonic resonance can cause amplification of harmonic
voltage (parallel resonance) or harmonic current (series resonance). A detuning reactor is used to prevent
harmonic resonance, by purposefully shifting the capacitor circuit resonant
frequency beneath the lowest harmonic that is present. It also restricts the
flow of harmonic current into the capacitor by increasing the capacitor circuit
impedance relative to harmonic frequencies.
Power factor capacitor systems that use detuning reactors are sometimes
referred to as anti-resonant capacitors, capacitors with harmonic blocking
reactors, or simply detuned capacitors.
Wednesday, June 27, 2012
Is it OK to add power factor capacitors to a power system that supplies motor drives? PQM-103
Adjustable speed motor drives (ASDs. VFDs, VSDs) are
non-linear loads that produce harmonic current distortion during their normal
operation. Harmonics are currents flowing at frequencies which are multiples of
the fundamental frequency (ie: 50Hz, 60Hz).
Since capacitive reactance (ohms) decreases as frequency increases,
capacitors provide a low impedance path for harmonic currents. This can result
in the power factor capacitors absorbing significant harmonic currents and
becoming overloaded, leading to premature failure. Capacitance also combines with system
impedance (ie: power transformer) to form a tuned circuit. If this circuit is tuned near one of the
harmonic frequencies present, then a resonance condition occurs and either
harmonic current or voltage can be amplified.
When adding power factor capacitors to a power system shared
by both across the line started motors and adjustable speed drives, there are
two choices. 1) apply harmonic filters
to the drives, sufficient to suppress the system harmonic voltage
distortion to negligible levels, 2) use a detuned capacitor system (consists
of a detuning reactor in series with capacitor to force the tuning point below
the lowest order harmonic).
Wednesday, June 20, 2012
How does source impedance affect harmonic distortion? PQM_102
If we consider an individual non-linear load such as a
6-pulse rectifier, the input harmonic current distortion is largely a function
of effective source impedance. Generally speaking, the higher the total input
impedance, the lower the harmonic current distortion. However, there is a point of diminishing
returns. Typical effective impedance values range from about 0.5%
(corresponding to about 100% THD-i) to about 5% (corresponding to about 35%
impedance). If a system had a total effective impedance of 10%, current
distortion would be about 26% THD-I. But, if the impedance was due to AC
reactance, then the corresponding ac voltage drop (about 10%) would be too high
for this to be a practical solution. While nameplate impedance (%) is based on
full rated current, effective impedance is based on actual circuit
(fundamental) current. If a 500KVA, 5%
impedance transformer supplies power to a 300KVA motor drive, then although
nameplate impedance states 5%, the effective impedance will be about 3% (5%
times 300/500) and harmonic current distortion at full load will be about 45%
THD-i. Current distortion, as a
percentage of fundamental current, will increase as load is reduced (lower
effective impedance), although the rms value of harmonic current will decrease.
.
Wednesday, June 13, 2012
Where does harmonic voltage distortion come from? PQM_101
Voltage
distortion is caused when harmonic currents flow through system impedance. Simply put,
when a piece of electronic equipment draws harmonic current, the harmonic currents flow though the power
source impedance (XL) and
voltage results at each harmonic frequency based on Ohm’s Law (amps times
ohms). The sources of harmonic voltage distortion are those electrical loads
the draw non-sinusoidal current.
On a 60 Hz
power system, 5th harmonic current is current flowing at 300 (5 x
60) Hz. Following ohms law, when
harmonic current flows though upstream impedance it will cause a voltage drop
at the same frequency. 5th
harmonic current will cause 5th harmonic voltage on the power system
that supplies this load. It is common to
all loads connected to the system.
Utilities
generate sinusoidal voltage, but power electronic loads in customer facilities
distort both current and voltage. To reduce power system harmonic voltage
distortion, one must typically identify the source of harmonic current and
minimize harmonic current distortion at this point.
Subscribe to:
Posts (Atom)